Disjuntor de caixa moldada NDM3A-630

Certificações disponíveis CE A disponibilidade depende do modelo e da configuração.
NDM3A-630 Molded Case Circuit Breaker(images 1)

The NDM3A-630 molded case circuit breaker (hereinafter referred to as circuit breaker) appliesto infrequent switching of circuits with the AC 50/60Hz, the working voltage of AC1000V and working current of 630A as well as infrequent motor starting. With the overload, short circuit and undervoltage protection functions, the circuit breaker can protect lines and power equipment from damage.

Technical Parameters

ModelNDM3A-630
Rated current of frame Inm(A)630
Rated current In(A)400,500,630
Rated insulation voltage Ui(AC V)1140
Rated impulse withstand voltage Uimp (V)8000
Rated working voltage Ue (AC V)550,600,690,800,1000
Power frequency withstand voltage U(1min)(V)3500
Utilization categoryA
Number of poles3
Breaking capacity levelM
Rated limit short-circuit breaking capacity Icu (kA)AC550V50
AC600V42
AC690V35
AC800V30
AC1000V12
Rated operating short-circuit breaking capacity Ics (kA)AC550V50
AC600V42
AC690V35
AC800V23
AC1000V12
 Operating performance (times)          Electrical lifeAC550V4000
AC600V2500
AC690V2000
AC800V1500
AC1000V1000
    Mechanical LifeMaintainable Free Life  10000
Maintainable Life  20000

Normal Working Environment
1)The altitude of the installation site doesn’t exceed 2,500m. See the “High-altitude DeratingFactor Table of Circuit Breaker” for the derating factor at the altitude;
2)The ambient temperature is -35℃ ~ + 70℃; the average within 24 h shall not be morethan +35℃. If the ambient temperature is higher than +40℃, the user needs to reduce thecapacity. See the “Derating Factor Table of Temperature Change for the Circuit Breaker”for the derating factor;
3)Its relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higherrelative humidity is allowed at a lower temperature. For example, the relative humidity at20℃ can reach 90%; for frost due to temperature change, the corresponding measuresshould be taken;
4)The product can withstand the effects of wet air, salt mist, oil mist and mould;
5)The installation category of the circuit breaker connected to the main loop is: Category Ⅲ (power distribution and control level), The installation category of the circuit breaker notconnected to the main loop is: Category Ⅱ (load level);
6)The pollution level is Level 3;
7)The product should be installed in places that are free from explosive media, mediacorrosive to metal, insulation damaging gas, and conductive dust, which should be alsoavoided from snow and rain;
8)In case of stricter user conditions than the above description, negotiate with themanufacturer.

NDM3A-630 Molded Case Circuit Breaker(images 2)
NDM3A-630 Molded Case Circuit Breaker(images 3)
NDM3A-630 Molded Case Circuit Breaker(images 4)
NDM3A-630 Molded Case Circuit Breaker(images 5)
ÚLTIMO: PRÓXIMO:

Recomendações relacionadas

  • NDQ3HP

    1299

    1、Application The NDQ3HP bypass automatic transfer switching equipment applies to the automatic transfer between two-way power supplies in the emergency power supply system with the AC rated working voltage of 415V and below, rated frequency of 5...

    Ver detalhes
  • NDB1-40 MCB miniature circuit breaker

    1094

    1.Application Scope NDB1-40 dedicated to the low voltage power distribution system of industrial, buildings, energy, communications and infrastructure. The MCB can cut off phase and neutral lines at the same time, whereas the neutral line should...

    Ver detalhes
  • NDM2E-400(M,H)

    1014

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2E-400 series of electronic molded case circuit breakers (hereinafter referred to as circuit breakers) apply to infrequent switching of circuits with the AC 50Hz, the working voltage of A...

    Ver detalhes
  • NDM2L-125

    1270

    1. Applicable Scope and Purpose of Circuit Breaker The NDM2L-125 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the w...

    Ver detalhes
Expandir mais!

Lista de produtos de consultoria