Applicable scope and purpose
● Short -circuit protection
● Over-load protection
● Control
● Isolation
● DC system protection
NDB2T-63 (UL489), destinado ao sistema de distribuição de energia de baixa tensão em ambientes industriais, edifícios, comunicações energéticas e infraestruturas.
Main technical specification
● Electrical parameters
○ Rated working voltage and relevant breaking capacity:
| Pole | 1P | 2P | 3P | 1P | 2P | 3P | |
| Rating current | 1~32A | 35~63A | |||||
| Item | Icu | ||||||
| Voltage | AC 120V | 10kA | — | — | 10kA | — | — |
| AC 240V | — | 10kA | 10kA | — | 10kA | 10kA | |
| AC 277V | 10kA | — | — | — | — | — | |
| AC 480Y/277V | — | 10kA | 10kA | — | — | — | |
| DC60V | 10kA | 10kA | — | 10kA | 10kA | — | |
| DC125V | — | 10kA | — | — | 10kA | — | |
○ Impulse withstand test voltages: 4kV
○ electrical endurance: 10000 times;Mechanical endurance: 20000 times
● Product certification and implementation standard.:
○ Product certificate:UL489;
○ Product certification standard:UL489;
● Environmental requirements:RoHS
● Isolation function
○ Practical breaking instructions
○ View window within the green identification said contact in the off position
● Tripping characteristic B type curve
○ Protection of short circuit current small load
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 4In(1±20%) C type curve
○ Protect normal load and distribution wire cable
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 8In(1±20%) D type curve
○ Protect starting current big impact load(Such as motor, transformer)
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping rang 12In(1±20%)
5、Normal working environment
● Ambient temperature:-40℃~+70℃
● Air relative humidity:≤95%
● Altitude:≤2000m
● pollution degree: 3
● Service place without significant vibration and impact
● Lower capacity coefflcient table above 2000 meters above sealevel

● Side-by-side volume reduction coefflcient table

6. Tripping characteristic

7、Outline dimensions

3P
8、Mounting
Modular construction,can be installed in EN60715 TH 35mm x 7.5mm standard guide rail.
9、Connect line requirements
○ Standard cross-sections of round copper conductors: 1~35mm2
○ Terminal screw: M5 ,Rated torque : 2.0N.m
11 、 Notice
1、Customers who disassemble the product without approval shall undertake relevant quality problems by themselves;
2、Do not touch the naked part of conductive components when the product is power on;
3、Don’t test characteristics of the breaker optionally, the manufacturer is irresponsible for such quality problems;
4、Keep wiring correct to prevent malfunction or damage of wiring terminals.
5、Please open the cover when installing the accessory. Please refer to OF2, SD2, MX+OF2 Instruction for details.
Especificações: Intervalo de corrente de disparo: Esquema elétrico; Dimensões gerais e de instalação (mm)
Ver detalhes1. Applicable Scope and Purpose The NDQ3-125 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product complies with the GB14048.1-2012 and GB/T14048.11-2016 standa...
Ver detalhes1. Applicable Scope and Purpose of Circuit Breaker The NDM2E-400 series of electronic molded case circuit breakers (hereinafter referred to as circuit breakers) apply to infrequent switching of circuits with the AC 50Hz, the working voltage of A...
Ver detalhes1. Applicable Scope and Purpose The NDQ3-800 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product complies with the GB14048.1-2012 and GB/T14048.11-2016 standards in acc...
Ver detalhes
Enviar um pedido de informação sobre o produto
Entraremos em contacto consigo no prazo de 24 horas